Application
HVAC, heating,energy-saving monitoring, heat balance regulation,heating regulation,AHU room,thermal energy transformation,etc.
Highlight :DN20~DN80 mm WiFi Ultrasonic Thermal Energy (BTU) Flow Meter, No need to set up pipe material , wireless communication ,precise measure flow and energy ,plug and play,alloy reinforced body.
Alloy reinforced version Clip-on WiFi Ultrasonic Thermal Energy Flow Meter
Flow Range: | 0.03m/s ~5.0m/s(0.1ft/s ~ ±16ft/s) | Accuracy: | ±2% | |
Pipe Diameter Range: | DN20~DN80mm | Measuring Medium: | Water | |
Pipe Material: | Stainless Steel/PVC/Copper/Stainless Steel | Communication Interface: | RS485,WiFi | |
Power Supply: | 10~36VDC/500mA | Keyboard: | 4 touch keys | |
Display: | 1.44 " LCD color screen, resolution 128 * 128 |
SLE3W Clip-on WiFi Ultrasonic Thermal Energy(BTU) Flow Meter
Alloy reinforced & compact all-in-one WiFi ultrasonic thermal energy(BTU) flow meter
Introduction
Gentos quick measure SLE3W adopts the ultrasonic transit time measurement principle, combined with Gentos patented flow algorithm technology, it realizes accurate measurement of the fluid flow and energy in the pipe. The product is all-in-one and clip-on structure design, which is simple and convenient to install. Only four steps are needed all along.The installation process requires no contact with fluid media and no need to shut down.
It adopts WiFi communication, implement cloud data storage, users can access cloud data anytime and anywhere through mobile and PC terminals,manage,analyze and query measurement data information.
Advantages
lWiFi communication
lAvailable on the MeterTube app & platform
lEasy installation, no damaging pipe
lNo adjustment,plug and play
lLCD color display
lScreen display in 4 direction rotation
Transmitter &Temperature Transducer Dimensions
SLE3W Transmitter Dimension
Pipe Diameter Comparison Table Unit:mm | ||||||||
Model | Nominal Inner Diameter of Pipe | W | W1 | L | L1 | H | Ø | |
SLE3W | DN20 | 60 | 51 | 105 | 118 | 121 | 29 | |
DN25 | 60 | 56 | 105 | 118 | 128 | 36 | ||
DN32 | 60 | 63 | 105 | 118 | 135 | 43 | ||
DN40 | 60 | 74 | 105 | 118 | 146 | 54 | ||
DN50 | 60 | 89 | 105 | 153 | 159 | 67 | ||
DN65 | 60 | 102 | 105 | 153 | 172 | 80 | ||
DN80 | 60 | 113 | 105 | 153 | 183 | 91 |
SLE3W Temperature Transducer Clamp Dimension
Pipe Size | Ø Pipe clamp inner diameter(mm) | Ø1 Pipe clamp outer diameter(mm) | ||
DN20 | 29 | 43 | ||
DN25 | 36 | 48 | ||
DN32 | 43 | 55 | ||
DN40 | 54 | 66 | ||
DN50 | 67 | 81 | ||
DN65 | 80 | 84 | ||
DN80 | 91 | 105 |